INSTALLATION
Wall Mounted 0121…0661
Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0. - Date: 18-07-2000 EN
9 (22)
mm
WMF
0551
WMF
0661
A1
1050 1050
B
2250 2250
C
625 625
S
x
(*)
300 300
D
x
(*)
300 300
H
300 300
E (*)
1500 1500
kg
300 320
(*) see par. ‘WORKING SPACE’
B
A
1
C
E
Fig. 6
D
x
H
S
x
H
Fig. 7
WM* 0551-0661
POSITIONING THE UNIT
WM units are designed to be installed outdoors. However, it is recommended to protect the unit from rain, snow or
water falling from drains or gutters.
The unit must be perfectly vertical with a maximum slope of 6-7 mm: a levelling defect can cause spillage from
the condensate tray.
Do not install the unit less than 200 metres from the sea or near spas with sulphurous springs. Make sure that
the unit cannot take in air which contains vapours of inflammable or greasy substances.
The air flow taken in by the fans via the condenser coil must not be obstructed in order not to reduce the
efficiency of the unit and to avoid the unit stopping because of the intervention of the compressor’s safety
functions;
If the installation location is windy, it is advised to choose a protected area since the condensate axial fans have
limited pressure (not greater than 10 Pa). See fig 5. and 7.
WORKING SPACE